Appendix
- 311 -
12
Para. No. Para. Name Setting Range Default Property Page
F3-16 Voltage decline time of V/F
separation
0.0s to 1000.0s 0.0s
ƿ
1
4
8
F3-17 Stop mode selection for V/F
separation
0: Frequency and voltage
declining to 0 independently
1: Frequency declining after
voltage declines to 0
0
ƿ
1
4
8
F3-18 Current limit level 50% to 200% 150%
ƾ
1
5
0
F3-19 Current limit selection 0: Disabled
1: Enabled
1
ƾ
1
5
0
F3-20 Current limit gain 0 to 100 20
ƿ
1
5
0
F3-21 Compensation factor of speed
multiplying current limit level
50% to 200% 50%
ƾ
1
5
0
F3-22 Voltage limit 650 to 800 V 770 V
ƾ
1
5
1
F3-23 Voltage limit selection 0: Disabled
1: Enabled
1
ƾ
1
5
1
F3-24 Frequency gain for voltage
limit
0 to 100 30
ƿ
1
5
1
F3-25 Voltage gain for voltage limit 0 to 100 30
ƿ
1
5
1
F3-26 Frequency rise threshold
during voltage limit
0 to 50 Hz 5 Hz
ƾ
1
5
1
Group F4: Input Terminals
F4-00 DI1 function selection
0: No function
1: Forward run (FWD)
2: Reverser run (REV)
3: Three-wire control
4: Forward jog (FJOG)
5: Reverse jog (RJOG)
6: Terminal UP
7: Terminal DOWN
8: Coast to stop
9: Fault reset (RESET)
10: RUN disabled
11: External fault normally-open
input
12: Multi-reference terminal 1
13: Multi-reference terminal 2
14: Multi-reference terminal 3
15: Multi-reference terminal 4
16: Terminal 1 for acceleration/
deceleration time selection
17: Terminal 2 for acceleration/
deceleration time selection
18: Frequency reference setting
channel switchover
19: UP and DOWN setting clear
(terminal, operation panel)
20: Command source switchover 1
1
ƾ
1
7
8