Appendix
- 319 -
12
Para. No. Para. Name Setting Range Default Property Page
Group F8: Auxiliary Functions
F8-00 Jog frequency reference 0.00 Hz to max. frequency 2.00 Hz
ƿ
2
0
0
F8-01 Jog acceleration time 0.0s to 6500.0s 20.0s
ƿ
2
0
0
F8-02 Jog deceleration time 0.0s to 6500.0s 20.0s
ƿ
2
0
0
F8-03 Acceleration time 2 0.0s to 6500.0s Model
dependent
ƿ
1
4
2
F8-04 Deceleration time 2 0.0s to 6500.0s Model
dependent
ƿ
1
4
2
F8-05 Acceleration time 3 0.0s to 6500.0s Model
dependent
ƿ
1
4
2
F8-06 Deceleration time 3 0.0s to 6500.0s Model
dependent
ƿ
1
4
2
F8-07 Acceleration time 4 0.0s to 6500.0s 0.0s
ƿ
1
4
2
F8-08 Deceleration time 4 0.0s to 6500.0s 0.0s
ƿ
1
4
2
F8-09 Frequency jump 1 0.00 Hz to max. frequency 0.00 Hz
ƿ
2
0
1
F8-10 Frequency jump 2 0.00 Hz to max. frequency 0.00 Hz
ƿ
2
0
1
F8-11 Frequency jump band 0.00 Hz to max. frequency 0.00 Hz
ƿ
2
0
1
F8-12 Forward/Reverse run switchover
dead-zone time
0.0s to 3000.0s 0.0s
ƿ
2
0
2
F8-13 Reverse RUN selection 0: Disabled
1: Enabled
0
ƿ
2
0
2
F8-14 Running mode when frequency
reference lower than frequency
lower limit
0: Run at frequency reference
lower limit
1: Stop
2: Run at zero speed
0
ƿ
1
3
5
F8-15 Droop rate 0.0% to 100.0%
0.0% to 100.0% correspond
to 0.00 to 10.00 on operating
panel.
0.00%
ƿ
-
F8-16 Accumulative power-on time
threshold
0 to 65000 h 0 h
ƿ
-
F8-17 Accumulative running time
threshold
0 to 65000 h 0 h
ƿ
-
F8-18 Startup protection selection 0: Disabled
1: Enabled
0
ƿ
-
F8-19 Frequency detection value 1 0.00 Hz to max. frequency 50.00 Hz
ƿ
2
0
3
F8-20 Frequency detection hysteresis 1 0.0% to 100.0% 5.0%
ƿ
2
0
3
F8-21 Detection width of target
frequency reached
0.0% to 100.0% 0.0%
ƿ
2
0
3
F8-22 Jump frequency function 0: Disabled
1: Enabled
0
ƿ
2
0
1
F8-25 Switchover frequency of accel
time 1 and accel time 2
0.00 Hz to max. frequency 0.00 Hz
ƿ
2
0
4
F8-26 Switchover frequency of decel
time 1 and decel time 2
0.00 Hz to max. frequency 0.00 Hz
ƿ
2
0
4
F8-27 Set highest priority to terminal
JOG function
0: Disabled
1: Enabled
0
ƿ
2
0
0

Table of Contents