Para. No. Para. Name Setting Range Default Property Page
FA-22 PID initial value active time 0.00s to 650.00s 0.00s
ƿ
1
2
8
FA-25 PID integral property 00 to 11
Whether to stop integral
operation when PID output
reaches the limit
0: Continue integral operation
1: Stop integral operation
Integral separation
0: Disabled
1: Enabled
00
ƿ
1
2
9
FA-26 Detection level of PID feedback
loss
0.0%: No detection
0.1% to 100.0%
0.0%
ƿ
1
2
9
FA-27 Detection time of PID feedback
loss
0.0s to 20.0s 0.0s
ƿ
1
2
9
FA-28 Selection of PID operation at stop 0: Disabled
1: Enabled
0
ƿ
1
2
9
Group Fb: Wobble Function, Fixed Length and Count
Fb-00 Wobble setting mode 0: Relative to the frequency
reference
1: Relative to the max.
frequency
0
ƿ
1
6
7
Fb-01 Wobble amplitude 0.0% to 100.0% 0.0%
ƿ
1
6
7
Fb-02 Wobble step 0.0% to 50.0% 0.0%
ƿ
1
6
7
Fb-03 Wobble cycle 0.0s to 3000.0s 10.0s
ƿ
1
6
7
Fb-04 Triangular wave rising time
FRHI¿FLHQW
0.0% to 100.0% 50.0%
ƿ
1
6
7
Fb-05 Set length 0 to 65535 m 1000 m
ƿ
1
6
8
Fb-06 Actual length 0 to 65535 m 0 m
ƿ
1
6
8
Fb-07 Number of pulses per meter 0.1 to 6553.5 100.0
ƿ
1
6
8
Fb-08 Set count value 1 to 65535 1000
ƿ
1
6
9
Fb-09 Designated count value 1 to 65535 1000
ƿ
1
6
9
Group FC: Multi-Reference and Simple PLC Function
FC-00 Reference 0 -100.0% to 100.0% 0.0%
ƿ
1
1
9
FC-01 Reference 1 -100.0% to 100.0% 0.0%
ƿ
1
1
9
FC-02 Reference 2 -100.0% to 100.0% 0.0%
ƿ
1
1
9
FC-03 Reference 3 -100.0% to 100.0% 0.0%
ƿ
1
1
9
FC-04 Reference 4 -100.0% to 100.0% 0.0%
ƿ
1
1
9
FC-05 Reference 5 -100.0% to 100.0% 0.0%
ƿ
1
1
9
FC-06 Reference 6 -100.0% to 100.0% 0.0%
ƿ
1
1
9
FC-07 Reference 7 -100.0% to 100.0% 0.0%
ƿ
1
1
9
FC-08 Reference 8 -100.0% to 100.0% 0.0%
ƿ
1
1
9
FC-09 Reference 9 -100.0% to 100.0% 0.0%
ƿ
1
1
9