3. Electrical Installation
- 62 -
3
Table 3-12 Models and dimensions of the JST crimp terminal above
Model Dimensions (mm) Crimping Tool
No.
d2 (Min.) B (Max.) L F E D d1 T
150-12 13.0 36.0 66.0 23.0 27.0 26.5 19.5 3.2 YPT-150-1
250-12 13.0 44.0 78.0 24.5 31.5 35.6 26.0 4.5 YF-1, YET-300-1
250-12 13.0 44.0 78.0 24.5 31.5 35.6 26.0 4.5 YF-1, YET-300-1
250-16 17.0 44.0 78.0 24.5 31.5 35.6 26.0 4.5 YF-1, YET-300-1
325-16 17.0 50.5 88.0 33.5 35.5 37.6 28.0 4.5 YF-1, YET-300-1
3.2.2 Main Circuit Cable Recommendations
Ƶ
Main Circuit Cable Selection
Inovance recommends symmetrical shielded cable as main circuit cable, which can
reduce electromagnetic radiation of entire conductive system compared with four-
conductor cable
Figure 3-15 Symmetrical shielded cable is recommended
PE
PE conductor
and shield
Shield Shield
PE
PE
Shield