6. Description of Parameters
- 161 -
6
Function Code Parameter Name Setting Range Default
F7-03
LED display
running
parameters 1
0000 to FFFF
7 6 5 4 3 2 1 0
Running frequency 1 (Hz)
Frequency reference (Hz)
Bus voltage (V)
Output voltage (V)
Output current (A)
Output power (kW)
Reserved
DI state (V)
15 14 12 11 10 9 8
DO state
AI1 voltage (V)
Count value
Length value
Load speed display
PID reference
13
AI2 voltage (V)
AI3 voltage (V)
If a parameter needs to be displayed during
running, set corresponding bit to 1, and set F7-03 to
hexadecimal equivalent.
1F
F7-04
LED display
running
parameters 2
0000 to FFFF
7 6 5 4 3 2 1 0
PID feedback
PLC stage
Pulse reference (kHz)
Running frequency 2
Remaining running time
AI1 voltage before correction
AI2 voltage before correction
AI3 voltage before correction
15 14 12 11 10 9 8
Motor speed
Current power-on time (H)
Current running time (Min)
Pulse reference (Hz)
Communication reference
Reserved
Main frequency display (Hz)
Auxiliary frequency display (Hz)
13
If a parameter needs to be displayed during
running, set corresponding bit to 1, and set F7-04 to
hexadecimal equivalent.
0