Appendix
- 321 -
12
Para. No. Para. Name Setting Range Default Property Page
Group F9: Fault and Protection
F9-00 Motor overload protection 0: Disabled
1: Enabled
1
ƿ
1
5
3
F9-01 Motor overload protection gain 0.20 to 10.00 1.00
ƿ
1
5
3
F9-02 Motor overload pre-warning
FRHI¿FLHQW
50% to 100% 80%
ƿ
1
5
4
F9-07 Detection of short-circuit to
ground upon power-on
Short-circuit to ground
protection before running
0: Disabled
1: Enabled
Short-circuit to ground
protection at power-on
0: Disabled
1: Enabled
01
ƿ
-
F9-08 Braking unit applied voltage 650 to 800 V 760 V
ƾ
1
5
1
F9-09 Auto reset times 0 to 20 0
ƿ
1
5
5
F9-10 Selection of DO action during
auto reset
0: Not act
1: Act
0
ƿ
1
5
5
F9-11 Delay of auto reset 0.1s to 100.0s 1.0s
ƿ
1
5
5
F9-12 Input phase loss/pre-charge relay
protection
0: Disabled
1: Enabled
Input phase loss
0: Disabled
1: Enabled
Pre-charge relay protection
11
ƿ
1
5
4
F9-13 Output phase loss protection
During running
0: Disabled
1: Enabled
Before running
0: Disabled
1: Enabled
01
ƿ
1
5
5
F9-14 1st fault type 0: No fault
1: Reserved
2: Overcurrent during
acceleration
3: Overcurrent during
deceleration
4: Overcurrent at constant
speed
- Ɣ -