Appendix
- 324 -
12
Para. No. Para. Name Setting Range Default Property Page
F9-49 Fault protection action selection 3 00000 to 22222
User-defined fault 1 (Err27):
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Accumulative power-on time
reached (Err29):
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
PID feedback lost during running
(Err31):
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Load loss (Err30):
0: Coast to stop
1: Decelerate to stop
2: Continue to run at 7% of rated
motor frequency and restore to
the frequency reference if the load
recovers
User-defined fault 2 (Err28):
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
00000
ƿ
-
F9-54 Frequency selection for continuing
to run upon fault
0: Current running frequency
1: Frequency reference
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon
abnormality
0
ƿ
1
5
6
F9-55 Backup frequency upon fault 0.0% to 100.0% (max.
frequency)
100.0%
ƿ
1
5
6
F9-56 Type of motor temperature sensor 0: No temperature sensor
1: PT100
2: PT1000
0
ƿ
1
5
7
F9-57 Motor overheat protection
threshold
0°C to 200°C 110°C
ƿ
1
5
7
F9-58 Motor overheat pre-warning
threshold
0°C to 200°C 90°C
ƿ
1
5
7
F9-59 Power dip ride-through function
selection
0: Disabled
1: Bus voltage constant control
2: Decelerate to stop
0
ƾ
1
5
8
F9-60 Threshold of power dip ride-
through function disabled
80% to 100% 85%
ƾ
1
5
8
F9-61 Judging time of bus voltage
recovering from power dip
0.0s to 100.0s 0.5s
ƾ
1
5
8
F9-62 Threshold of power dip ride-
through function enabled
60% to 100% 80%
ƾ
1
5
8
F9-63 Load lost protection 0: Disabled
1: Enabled
0
ƿ
1
5
8
F9-64 Load lost detection level 0.0% to 100.0% 10.0%
ƿ
1
5
8
F9-65 Load lost detection time 0.0s to 60.0s 1.0s
ƿ
1
5
8
F9-71 Power dip ride-through gain Kp 0 to 100 40
ƿ
1
5
8
F9-72 Power dip ride-through integral
FRHI¿FLHQW
0 to 100 30
ƿ
1
5
8
F9-73 Deceleration time of power dip
ride-through
0.0s to 300.0s 20.0s
ƾ
1
5
8