EasyManua.ls Logo

Inovance MD290T45G/55P - Page 53

Inovance MD290T45G/55P
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3. Electrical Installation
- 52 -
3
Figure 3-3 Terminal dimensions of MD290T45G/55P and MD290T55G/75P
R S
POWER
T
BR
(+)
(-)
V
U
W
MOTOR
248
11
M8 flat washer
+ spring washer
+ nut
26.8
24.8
111
31
M8
combination
screw
Table 3-4 Recommended cable dimensions and tightening torque of MD290T45G/55P and
MD290T55G/75P
AC Drive Model Rated Input
Current (A)
Power Input/
Output Cable
Crimp
Terminal
Model
Ground
Cable
Crimp
Terminal
Model
Tightening
Torque (N·m)
Screw
Spec.
MD290T45G 89 3 x 35 mm
2
3 x 2 AWG
22-8 25 mm
2
6 AWG
14-8 10.5 M8
MD290T55P 111 3 x 50 mm
2
3 x 1/0 AWG
60-8 25 mm
2
6 AWG
14-8 10.5 M8
MD290T55G 106 3 x 50 mm
2
3 x 1/0 AWG
60-8 25 mm
2
6 AWG
14-8 10.5 M8
MD290T75P 143
3 x 70 mm
2
3 x 2/0 AWG
70-12 35 mm
2
4 AWG
22-12 10.5 M12

Table of Contents

Related product manuals