EasyManua.ls Logo

Inovance MD290T45G/55P - Page 52

Inovance MD290T45G/55P
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3. Electrical Installation
- 51 -
3
Figure 3-2 Terminal dimensions of MD290T30G/37P and MD290T37G/45P
16.5
20.2
1820.2
20
.2
20.2
161.6
M6 combination scre
w
RST UVW
POWER MOTOR
BR
(+) (-)
Table 3-3 Recommended cable dimensions and tightening torque of MD290T30GB/37P and
MD290T37GB/45P
AC Drive Model Rated Input
Current (A)
Power Input/
Output Cable
Crimp
Terminal
Model
Ground
Cable
Crimp
Terminal
Model
Tightening
Torque
(N·m)
Screw
Spec.
MD290T30G 57 3 x 16 mm
2
3 x 4 AWG
14-L6 16 mm
2
8 AWG
8-6 4.0 M6
MD290T37P 71 3 x 16 mm
2
3 x 4 AWG
14-L6 16 mm
2
8 AWG
8-6 4.0 M6
MD290T37G 69 3 x 16 mm
2
3 x 4 AWG
14-L6 16 mm
2
8 AWG
8-6 4.0 M6
MD290T45P 86 3 x 25 mm
2
3 x 3 AWG
22-8
25 mm
2
6 AWG
14-8
4.0 M6

Table of Contents

Related product manuals