3. Electrical Installation
- 53 -
3
Figure 3-4 Terminal dimensions of MD290T75G/90P to MD290T110G/132P
280
35
32
30.6
148.5
M12
flat washer + spring washer + nut
RS
TUVW
POWER MOTOR
BR (+) (-)
16
Table 3-5 Recommended cable dimensions and tightening torque of MD290T75G/90P to
MD290T110G/132P
AC Drive Model Rated Input
Current (A)
Input/Output
Power Cable
Crimp
Terminal
Model
Ground
Cable
Crimp
Terminal
Model
Tightening
Torque (N·m)
Screw
Spec.
MD290T75G 139 3 x 70 mm
2
3 x 2/0 AWG
70-12 35 mm
2
4 AWG
22-12 35.0 M12
MD290T90P 167 3 x 95 mm
2
3 x 3/0 AWG
80-12 50 mm
2
4 AWG
22-12 35.0 M12
MD290T90G 164 3 x 95 mm
2
3 x 3/0 AWG
80-12 50 mm
2
4 AWG
22-12 35.0 M12
MD290T110P 198 3 x 120 mm
2
3 x 4/0 AWGl
100-12 70 mm
2
3 AWG
38-12 35.0 M12
MD290T110G 196 3 x 120 mm
2
3 x 4/0 AWGl
100-12 70 mm
2
3 AWG
38-12 35.0 M12
MD290T132P 239
3 x 150 mm
2
350 kcmil
150-12 95 mm
2
2 AWG
38-12 35.0 M12