3 Easy Setup
- 22 -
Step 12: Set DC Injection Braking/Pre-excitation If Needed
Para� No� Para� Name Setting Range Unit Default Commission
F6-00 Start mode 0: Direct startup
1: Reserved
2: Pre-excited startup
N�A� 0
F6-05 DC injection braking 1
level
0 to 100 % 0
F6-06 DC injection braking 1
active time
0�0 to 100�0 s 0�0
F6-11 DC injection braking 2
frequency threshold
0�00 to 10�00 Hz 0�00
F6-12 DC injection braking 2
delay time
0�0 to 100�0 s 0�0
F6-13 DC injection braking 2
level
0 to 100 % 50
F6-14 DC injection braking 2
active time
0�0 to 100�0 s 0�0
Note
Only when F6-00 = 0, parameters F6-05 and F6-06 are related to DC injection braking 1�
Para� No� Para� Name Setting Range Unit Default Commission
F6-00 Start mode 0: Direct startup
1: Reserved
2: Pre-excited startup (asynchronous motor)
N�A� 0 2
F6-05 Pre-excitation level 0 to 100 % 50
F6-06 Pre-excitation active
time
0�0 to 100�0 s 0�0
Note
Only when F6-00 = 2, parameters F6-05 and F6-06 are related to pre-excitation�
Step 13: Set PI of Velocity Loop If It’s SVC Control Mode
Para� No� Para� Name Setting Range Unit Default Commission
F2-00 Speed loop proportional
gain 1
1 to 100 N�A� 30
F2-01 Speed loop integral time 1 0�01 to 10�00 s 0�50
F2-02 Switchover frequency 1 0�00 to F2-05 Hz 5�00
F2-03 Speed loop proportional
gain 2
1 to 100 N�A� 20
F2-04 Speed loop integral time 2 0�01 to10�00 s 1�00

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inovance MD310 T7.5B and is the answer not in the manual?

Inovance MD310 T7.5B Specifications

General IconGeneral
Power7.5 kW
Control ModeV/F control, sensorless vector control, closed-loop vector control
Frequency Range0.00 Hz to 400.00 Hz
Storage Temperature-20°C to +60°C
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, overvoltage, undervoltage, overload, overheat
Communication InterfaceRS485
Ambient Temperature-10°C to +40°C
Humidity5% to 95% (non-condensing)
AltitudeUp to 1000m
Input Voltage3-phase 380V (-15%) - 440V (+10%)
Power Supply Voltage3-phase 380V (-15%) - 440V (+10%)

Related product manuals