6. Description of Parameters                                                                                                                   
- 192 -
6.11  Auxiliary Function
6.11.1  Jog
Jog is used to test equipment. In jog running, F6-00 must be set to 0 (direct start) and F6-10 
must be set to 0 (Decelerate to stop).
Function Code Parameter Name Setting Range Default
F0-25
Acceleration/Deceleration 
time base frequency
0: Maximum frequency (F0-10)
1: Frequency reference
2: 100 Hz
0
F8-00
Jog frequency reference 0.00 Hz to maximum frequency 2.00 Hz
F8-01
Jog acceleration time 0.0s  to 6500.0s 20.0s
F8-02
Jog deceleration time 0.0s to 6500.0s 20.0s
Jog acceleration time indicate time to accelerate from 0 Hz to F0-25.
Jog deceleration time indicate time to decelerate from F0-25 to 0 Hz.
Function Code Parameter Name Setting Range Default
F8-27
Set highest priority to 
terminal JOG function
0: Disabled
1: Enabled
0
This function parameter determines whether to set the highest priority to terminal JOG function. 
If this function is enabled and any of F4-00 to F4-09 is set to 4 (forward jog) or 5 (reverse jog) 
becomes active, the AC drive enters jog running status immediately.
Figure 6-59 Jog running
F8-01
Time(t)
Output frequency
F0-25
Set acceleration time
Set deceleration time
Actual acceleration time
Actual deceleration time
F8-02
F8-00
Jog command
Follow the steps below to control the drive jog via the operation panel.
Steps Forward jog Reverse jog
1
Set F7-01 = 3 to allocate the MF.K key with 
forward jog.
Set F7-01 = 4 to allocate the MF.K key 
with reverse jog.
Set F8-13 = 0 to allow reverse running.
2
Set F0-02 = 0 to select operation panel as 
command source.
Set F0-02 = 0 to select operation panel as 
command source.
3
Set F8-00, F8-01 and F8-02 properly. Set F8-00, F8-01 and F8-02 properly.
4
In stop status, press down the 
 key. 
The drive starts to jog in forward direction. 
After you release the  
 key, the AC drive 
decelerates to stop.
In stop status, press down the 
 key. 
The drive starts to jog in reverse direction. 
After you release the 
  key, the AC 
drive decelerates to stop.