11.3  Fault Display
When a fault occurs during running, the AC drive stops output immediately, the fault indicator
 
flashes, and contact of the fault relay acts. The operation panel displays the fault code such as 
, as shown in the following gure.
MF. K
RUN
STOP
RES
QUICK
PRG ENTER
RUN
LOCAL / REMOT FED / REV TUNE / TC
RPM
%
A VHz
RUN indicator
Fault dispay
RUN
Stop/ Reset
Unit indicator
Tuning/Torque 
control/Fault indicator
11.4  Resetting Fault
Stage Solution Remark
After the 
fault occurs
Check operating panel for detailed information of  
recent three faults, such as fault type and frequency, 
current, bus voltage, DI/DO state, accumulative 
power-on time and accumulative running time at 
occurrence of the faults. 
View these information via F9-14 
to F9-44.
Before 
the fault is 
reset
Find and remove cause of the fault. Then follow steps 
below to reset the fault.
Troubleshoot the fault according 
to section 11.5 "Faults and 
Diagnostics".
Fault 
resetting 
method
Fault resetting through a DI terminal
Allocate a DI terminal with function 9 “Fault reset 
(RESET)” by setting any of F4-00 to F4-09 to 9.
Fault resetting via operating panel
Conrm that F7-02 = 1 (default value). Then press 
the  
 key on operating panel.
MF
.K
RUN
STOP
RES
QUICK
PRG ENTER
STOP
RES
Automatic resetting
Disconnect the power supply. Until the fault code 
disappears, connect the power supply again.
Fault resetting via host computer
Conrm that F0-02 = 2 and write "7" (fault reset) to 
communication address 2000H.