Electrical Installation
‑45‑
Type
Terminal
Symbol
Terminal
Name
Function
Digital
output
DO1‑CME DO1
Photocoupler isolation and bipolar open collector
output
● Operating voltage range: 0 V to 24 V
● Output current range: 0 mA to 50mA
Note that digital output ground CME and digital
input ground COM are internally insulated, but are
shorted externally by jumper as the factory settings.
In this case, DO1 is driven by +24V by default. To
drive DO1 by external power supply, remove the
jumper between CME and COM.
FM‑COM
High‑speed
pulse output
The terminal is set by F5‑00 (FM terminal output
selection). When the terminal is used for high‑speed
pulse output, the maximum frequency is 100 kHz.
When the terminal is used for collector open
output, it has the same specifications as DO1.
Relay
output
T/A
Common
terminal
Driving capacity of the contact:
● 250 VAC, 3 A, COSØ=0.4
● 30 VDC, 1 A
T/B Normally
closed (NC)
terminal
T/C Normally
open terminal
Auxili
ary
inter
face
J4
Local PG card
interface
It is used to connect the resolver, differential, and
23‑bit encoders.
J11
External
operating
panel
interface
It is used to connect the external LCD operating
panel (SOP‑20‑810) or the LED operating panel
(MDKE‑10).
J13
Expansion
card interface
28‑core terminal for connection with expansion
cards, including I/O cards, communication cards,
and PG card
J14
STO terminal For details, see "
Table 2–4 STO terminal
descriptions
"
on page 46
.
DIP
switch
S1
For details, see "
Table 2–5 DIP switch descriptions
"
on page 46
.
S2
S3
S4
Current/Voltage mode selection for AO1
● On: Current output mode
● Off: Voltage output mode