Mechanical Installation
‑24‑
Table 1–5 Outline dimensions and mounting dimensions of T10 to T12 models (with AC output
reactor)
Stru
ctur
e
Mounting Hole
mm (in.)
Overall Dimension
mm (in.)
Mounting
Hole
Diameter
mm (in.)
Weight
kg (lb)
A1 A2 B1 B2 H H1 W W1 D D1
T10
240
(9.5)
150
(5.9)
1035
(40.8)
424
(16.7)
1424
(56.1)
1472
(58.0)
300
(11.8)
360
(14.2)
500
(19.7)
φ13 (0.5) 160 (352.7)
T11
225
‑8.9
185
(7.3)
1175
(46.3)
435
(17.1)
1586
(62.5)
1622
(63.9)
330
(13.0)
390
(15.4)
545
(21.5)
φ13 (0.5) 215 (474.0)
T12
240
‑9.5
200
(7.9)
1280
(50.4)
432
(17.0)
1683
(66.3)
1733
(68.3)
340
(13.4)
400
(15.8)
545
(21.5)
φ16 (0.6) 245 (540.1)
1.2.3 Installation Within the Cabinet
CCoonntteexxtt
The nine‑fold profile cabinet (PS cabinet) is recommended. This kind of cabinet is in
an assembled structure, which is cost effective. The openings on the main column of
the cabinet meet the general standards, facilitating the design of mounting beams
and structure strengthening. In summary, the nine‑fold profile cabinet is a kind of
industrial standard cabinet with high reliability. "
Figure 1–8
"
on page 24
shows the
cross section of the nine‑fold profile cabinet.
PPrroocceedduurree
1. In the nine‑fold profile cabinet (PS cabinet), install the mounting beam for fixing
the AC drive and reserve fixed holes.
Figure 1‑8 Top view of the cabinet for T11 and T12 models
To install T11 to T12 models into the nine‑fold profile cabinet with the depth of 600
mm, bend the back mounting board inwards (not required for the cabinet with the
depth of 800 mm), as shown in "
Figure 1–9
"
on page 25
. However, if the cabinet
with the depth of 600 mm has both front and back doors, the AC drive cannot be
installed in this kind of cabinet. Instead, install the AC drive into the cabinet with
the depth of 800 mm.