Commissioning and Trial Run
‑42‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
(continued) 62720 DO1/RO1 hardware
source
202: Expansion card 2 ‑
DO2/RO2
203: Expansion card 2 ‑
DO3/RO3
204: Expansion card 2 ‑
DO4/RO4
205: Expansion card 2 ‑
DO5/RO5
206: Expansion card 2 ‑
DO6/RO6
207: Expansion card 2 ‑
DO7/RO7
208: Expansion card 2 ‑
DO8/RO8
0 ‑ Modifiable
only at stop
F5‑01 62721 DO1/RO1 function
selection
0: No function
1: Ready to run
2: Faulty
3: Warning
4: Circuit breaker action
5: Bus undervoltage
6: Bus overvoltage
7: Bus voltage normal
8: Three‑phase input
abnormal
9: Three‑phase input
normal
10: IGBT over‑temperature
output
11: IGBT over‑temperature
pre‑warning output
12: Communication
control
0 ‑ Modifiable
only at stop
F5‑02 62722 DO2/RO2 hardware
source
Same as F5‑00 0 ‑ Modifiable
only at stop
F5‑03 62723 DO2/RO2 function
selection
Same as F5‑01 0 ‑ Modifiable
only at stop
F5‑04 62724 DO3/RO3 hardware
source
Same as F5‑00 0 ‑ Modifiable
only at stop
F5‑05 62725 DO3/RO3 function
selection
Same as F5‑01 0 ‑ Modifiable
only at stop
F5‑06 62726 DO4/RO4 hardware
source
Same as F5‑00 0 ‑ Modifiable
only at stop
F5‑07 62727 DO4/RO4 function
selection
Same as F5‑01 0 ‑ Modifiable
only at stop
F5‑08 62728 DO5/RO5 hardware
source
Same as F5‑00 0 ‑ Modifiable
only at stop