6 Parameter Description
- 
182
 -
Group F0: Basic parameters
Function 
Code
Name Setting Range Default Unit Property
F0-00 Control mode
0: Sensorless vector control 
(SVC)
1: Closed-loop vector control 
(CLVC)
2: Voltage/Frequency (V/F) 
control
1 -
★
It is used to set the control mode of the system, as described in the following table.
Value
Control 
mode
Function
Require 
Encoder?
0
Sensorless 
vector 
control 
(SVC)
It is applicable to:
Low-speed running during no-load commissioning 
and fault judgment at inspection of the asynchronous 
motor
Synchronous motor running on special conditions 
(used only by professional engineers, not described in 
this manual)
No
1
Closed-
loop 
vector 
control 
(CLVC)
It is applicable to normal running in distance control. Yes
2
Voltage/
Frequency 
(V/F) 
control
It is applicable to equipment detection
(the ratio between the voltage and the frequency is 
torque feature is poor).
No
Function 
Code
Name Setting Range Default Unit Property
F0-01
Command source 
selection
0: Operation panel 
control
1: Distance control
1 -
★
It is used to set the source of running commands and running speed references, as 
described in the following table.
Value
Running 
Mode
Working Mode
Purpose Remarks
X Input Y Output
0
Operation 
panel 
control
Not 
detect 
X input 
signals
Not output
(The relay 
for the RUN 
contactor will 
output during 
motor auto-
tuning.)
Used only 
during motor 
test or no-
load auto-
tuning
The controller is 
operated by pressing 
RUN and STOP on the 
operation panel, and 
the running speed is 
set by F0-02 
(Running speed under 
operation panel 
control)