6 Parameter Description 
- 
191
 -
Group F3: Running control parameters
Function 
Code
Name Setting Range Default
Unit Property
F3-00 Startup speed 0.000 to 0.050 0.000 m/s
★
F3-01
Startup speed holding 
time
0.000 to 5.000 0.000 s
★
These two parameters are used to set the startup speed and startup speed holding 
time of the system. Refer to Figure 6-2  Running speed curve.
The parameters may reduce the terrace feeling at startup due to static friction 
between the guide rail and the guide shoes.
Function 
Code
Name Setting Range Default Unit Property
F3-02 Acceleration rate 0.200 to 1.500 0.700 m/s
2
★
F3-03
Acceleration start jerk 
time
0.300 to 4.000 1.500 s
★
F3-04 Acceleration end jerk time 0.300 to 4.000 1.500 s
★
F3-02, F3-03, and F3-04 are used to set the running curve during acceleration of the 
elevator, as shown in Figures 6-2 and 6-3.
F3-02 is the acceleration rate of the elevator speed curve (uniform acceleration seg-
ment).
F3-03 is the time for the rate to increase from 0 to the value set in F3-02 in the speed 
curve (start jerk segment). The larger the value is, the smoother the jerk is.
F3-04 is the time for the rate to decrease from the value set in F3-02 to 0 in the speed 
curve (end jerk segment). The larger the value is, the smoother the jerk is.
Function 
Code
Name Setting Range Default Unit Property
F3-05 Deceleration rate 0.200 to 1.500 0.700 m/s
2
★
F3-06 Deceleration end jerk time 0.300 to 4.000 1.500 s
★
F3-07 Deceleration start jerk time 0.300 to 4.000 1.500 s
★
F3-05, F3-06, and F3-07 are used to set the running curve during deceleration of the 
elevator, as shown in Figures 6-2 and 6-3.
F3-05 is the acceleration rate of the elevator speed curve (uniform deceleration 
segment).
F3-06 is the time for the rate to decrease from the value set in F3-05 to 0 in the speed 
curve (end jerk segment). The larger the value is, the smoother the jerk is.
F3-07 is the time for the rate to increase from 0 to the value set in F3-05 in the speed