6 Parameter Description 
- 
195
 -
Function 
Code
Name Setting Range Default Unit Property
F3-22
Acceleration rate at emergency 
evacuation
0.300 to 1.300 0.300 m/s
2
★
F3-22 is used to set the acceleration rate at emergency evacuation.
Function 
Code
Name Setting Range Default Unit Property
F3-23
Slow-down delay deceleration 
time
0.00 to 10.00 0 s
★
F3-23 indicates that the speed is reduced to 0.1 m/s within this time in case of slow-
-
to-tuning.
Function 
Code
Name Setting Range Default Unit Property
F3-24 Program function selection
0: Reserved
1: Slip 
experiment 
function 
enabled
2: UCMP test 
function 
enabled
0 -
★
This parameter is used when the motor slip experiment is performed during elevator 
acceptance. If the slip experiment onsite is not successful, set this parameter to 1 to 
enable the slip experiment function. After the experiment is completed, set F3-24 to 0 
to disable the function. When F3-24 is set to 2, it indicates that the UCMP test is per-
formed.
Function 
Code
Name Setting Range Default Unit Property
F3-25 Emergency electric RUN speed 0.100 to 0.300 0.250 m/s
★
F3-25 is used to set the elevator speed during emergency drive running.
Function 
Code
Name Setting Range Default Unit Property
F3-26 Shaft auto-tuning speed 0.250 to 0.630 0.250 m/s
★
F3-26 is used to set the elevator speed during shaft auto-tuning.