10.6 Weather– compensation adjustment
When an external sensor is connected the supply temperature is adjusted
automatically depending on the outside temperature, in accordance with the heating
line set. The maximum supply temperature (Tmax) is set via the main display. If
desired, the heating line can be changed in the parameter list. See § 10.3.
Heating line graph
X. Outside T in °C
Y. Supply T in °C
A. Factory setting
(Tmax CH = 80°C, Tmin CH = 25°C, Tmin out = -7°C, Tmax out = 25°C)
B. Example
(Tmax CH = 60°C, Tmin CH = 25°C, Tmin out= -7°C, Tmax out = 25°C)