P/N 145797999-2 • REV B • ISS 19MAR12    9 / 64 
b.  The red and yellow LEDs are blinking 
simultaneously then the field of view is 
obstructed and is insufficient to verify an 
alarm. 
There are two options: 
•  If the blinking started near the end of the 
detection area, you need to align the beam 
to the left (Figure 20, item 2). 
•  If the blinking started near the start of the 
detection area, you need to align the beam 
to the right (Figure 20, item 3). 
Loosen the base fixation screws (see Figure 4) 
and use the three adjustment screws in the 
base to realign the beam to the centre, as 
shown in Figure 20. When the beam is correctly 
realigned, retighten the base fixation screws. 
4.  If the LEDs do not blink, the curtain is outside of 
the detection range (Figure 20, item 4). Walk 
across the beam at a shorter distance to try to 
detect it. 
5.  Redo walk test to confirm that the detector is 
correctly aligned. 
6.  Put J2 to Off. 
Notes 
•  If the CLM is on, the alarm output is activated.  
•  It is recommended to place the cover on the 
detector during the CLM walk test.  
Identifying detector status by the LEDs 
Table 2: LED indication 
Detector 
status 
Yellow 
LED 
Red 
LED 
Description 
Power On  
   
Blinks alternatively for 
50 s 
Alarm 
 
 
On during alarm period 
— nominally for 3 s 
Trouble 
 
 
Continuously on 
High/Low 
voltage 
   
On until correct voltage is 
restored 
 = On steady      = Blinking (1 Hz)  
General information 
Latching 
When using multiple detectors in a single loop, wire 
for day/night (D/N) and walk test (WT) inputs, as 
shown in Figure 6. 
Remotely enabling/disabling the walk test LED 
See Figure 6. 
Disconnect the CV to terminal 10 (D/N) and 
connect it to terminal 11. The detector’s LED will 
blink as the alarm relay opens and closes. The walk 
test can now be carried out. 
Note: Only enabling the walk test will not clear the 
alarm memory. After disarming the system 
following an alarm, switch the walk test to On. 
When you switch walk test to Off, the indication of 
memorised alarms will reappear. Only when CV is 
re-applied to terminal 10 (i.e., the system is 
rearmed) will the memory be cleared and the LEDs 
turned off. 
To enable the walk test LED without a remote CV 
input, set DIP switch 4 to the On position. After 
walk test, set DIP switch 4 to the Off position. 
We recommend that the detector is regularly walk 
tested and the communication with the control 
panel checked. 
Setting the alarm memory 
See Figure 6. 
Note: First set the appropriate active polarity of the 
control voltage (CV) using the PIR DIP switch 1. 
Connect the CV to terminal 10 when the system is 
armed. When the system is disarmed, disconnect 
the CV. If an alarm occurs during the armed period, 
a flashing red LED will indicate which the 
detector(s) caused the alarm. Re-applying the CV 
(re-arming the system) will reset the LED indication 
and memory. 
Selecting the coverage pattern 
See Figures 21 and 22. 
The coverage pattern can be changed to fit specific 
requirements by using the mirror stickers 
(enclosed), as shown. We recommend that you 
blind unused curtains that are looking at objects 
located very close to the detector.