Object Description
A/B
Battery +/Battery -
C/D
PV1+/PV1-
J/K
PV2+/PV2-
E
DC switch
F WiFi port for external WiFi
L
Reserved port
G
DRM/BMS
H
Grid current / DRY IO
M
USB port for upgrading
N
POWER CAN /LEAD-NTC
I
Pressure valve
O
EPS output
P
Grid output
4. Technical Data
1. DC input (apply to version E, I)
Max. DC voltage[V]
550 550 550
MPPT voltage range [V]
125-550 125-550 125-550
Max. input current [A]
10/10 10/10 10/10
Start input voltage [V]
125 125 125
No. of MPP trackers
2 2 2
Backfeed current to PV array
0 0 0
Model
BD3K6TL-RL1 BD4K6TL-RL1
BD5KTL-R L1
Introduction Technical Data
WARNING !
Qualified electrician will be required for the
installation.
3.4 Terminals of PV inverter
A B C D E
F G H I
J K L
M N O P
com
Model
BD3KTL-R L1
BD4KTL-RL1 BD5KTL-RL1
BD3K6TL-RL1
BD4K6TL-RL1 BD6KTL-RL1
Max.
recommended DC power [W]
4600
6000 7000
Max.
DC voltage[V]
500 500 500
Norminal
DC operating voltage[V]
360 360 360
MPPT
voltage range [V]
125-500 125-500 125-500
MPPT
voltage range@full load [V]
150-500 170-500 220-500
Max.
input current [A]
14/14 14/14 14/14
Max.
short circuit current [A]
14/14 14/14 14/14
Start
input voltage [V]
125
125 125
Start
output voltage [V]
150 150 150
No.
of MPP trackers
2 2 2
Strings
per MPP tracker
1 1 1
Backfeed
current to PV array
0 0 0
DC
disconnection swtich
/
4.2 AC output/input (apply to version E, I)
Model
BD3KTL-R L 1
BD4KTL-R L 1
BD5KTL-
RL1
BD3K6TL-RL1
BD4K6TL-RL1
BD6KTL-
RL1
AC
output
Norminal
AC power[VA]
3000/3600 4000/4600 5000/6000
Max.
apparent AC power[VA]
3000/3600 4000/4600 5000/6000
Rated
grid voltage(range)[V]
230 (176 to 270)
Rated
grid frequency[Hz] 50/60
Norminal
AC current[A]
13/16
17.4/20
21.7/26
Max.AC
current[A]
13/16
17.4/20
21.7/26
Displacement
power factor
0.8 leading...0.8 lagging
Total
harmonic distortion(THDI)
< 2%
Load
control
optional
AC
input
Norminal
AC power[VA]
3000/3600 4000/4600 5000/6000
Rated
grid voltage(range)[V]
230(176 to 270)
Rated
grid frequency[Hz]
50/60
Norminal
AC current[A] 13/16
17.4/20
21.7/26
Max.AC
current[A]
13/16
17.4/20
21.7/26
Displacement
power factor
0.8 leading...0.8 lagging
AC
inrush current
35 35 35