C.TY TNHH TỰ ĐỘNG HÓA VIỆT TRUNG 02413.281.181-
0989.984.666
Website:www.viet-trung.com.vn Đ/c:194-Nguyễn Trãi-Võ Cường-
TP.Bắc Ninh
P8.29~P8.31.
71
DIEN DAN BIEN TAN HTTP://BIENTAN.HNSV.COM
CHV160A
series
special
inverter
for
water
supply
Level
control
mode:
1:
W
hen
pool
level
changes
from
high
to
low,
and
the
level
is
higher
than
lower
limit
level,
system
runs
with
normal
setting
pressure
mode.W
hen
the
level
is
lower
than
lower
limit
level
and
higher
than
water
shortage
level,
system
runs
with
abnormal
spare
pressure
mode
(determined
by
P8.32);
when
the
level
is
lower
than
water
shortage
level,
system
stop
running.
2.
W
hen
pool
level
changes
from
low
level
to
high
level,
system
do
not
run
when
the
level
is
lower
than
the
lower
limit
level,
when
the
level
is
higher
than
lower
limit
level
and
lower
than
the
upper
limit
level,
system
run
with
spare
pressure
mode(determined
by
P8.32);
When
the
level
is
higher
than
upper
limit
level,
system
returns
to
run
with
normal
pressure.