Goodrive350 series high-performance multi-function inverter Chapter 6
-142-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P04.17
V/F voltage point
1 of motor 2
0.0%110.0% (rated voltage of motor 2)
00.0%
P04.18
V/F frequency
point 2 of motor 2
P04.16 P04.20
0.00Hz
P04.19
V/F voltage point
2 of motor 2
0.0%110.0% (rated voltage of motor 2)
00.0%
P04.20
V/F frequency
point 3 of motor 2
P04.18 P12.02 (rated frequency of asynchronous
motor 2)
Or P04.18 P12.16 (rated frequency of synchronous
motor 2)
0.00Hz
P04.21
V/F voltage point
3 of motor 2
0.0%110.0% (rated motor voltage)
00.0%
P04.22
V/F slip
compensation
gain of motor 2
0.0200.0%
0.0%
P04.23
Low-frequency
oscillation control
factor of motor 2
0100
10
P04.24
High-frequency
oscillation control
factor of motor 2
0100
10
P04.25
Oscillation
control threshold
of motor 2
0.00HzP00.03 (max. output frequency)
30.00Hz
P04.26
Energy-saving
run
0: No action
1: Automatic energy-saving operation
Under light-load state, the motor can adjust the
output voltage automatically to achieve
energy-saving purpose
0
P04.27
Channel of
voltage setup
0: Keypad; output voltage is determined by P04.28
1: AI1
2: AI2
3: AI3
4: HDIA
5: Multi-step (the set value is determined by P10
group)
6: PID
7: MODBUS communication
0