Goodrive300-16 special inverter for HVAC Appendix A
40
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
3:Reserved
Note: 1, 2 and 3 are extension functions which
need corresponding extension cards.
P00.03
Max. output
frequency
Max. (P00.04, 10.00)~400.00Hz
50.00Hz
P00.04
Upper limit
of running
frequency
P00.05~P00.03 (Max. output frequency)
50.00Hz
P00.05
Lower limit
of running
frequency
0.00Hz~P00.04 (Upper limit of running frequency)
0.00Hz
P00.06
A
frequency
command
0: Keypad
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDI setting
5: Simple PLC program setting
6: Multi-step speed running setting
7: PID1 control setting
8: MODBUS communication setting
9: Profibus/CANopen/BACnet/Devicenet
communication setting
10: Ethernet communication setting
11: Reserved
0
P00.07
B
frequency
command
2
P00.08
B
frequency
command
reference
0: Maximum output frequency
1: A frequency command
0
P00.09
Combination
of setting
source
0: A
1: B
2: A+B
3: A-B
4: Max (A, B)
5: Min (A, B)
0