Goodrive300-16 special inverter for HVAC Appendix A
41
Detailed instruction of parameters
0.00 Hz~P00.03 (Max. output frequency)
0: Runs at the default direction
1: Runs at the reverse direction
Carrier
frequency
setting
Motor
parameter
autotuning
0: No operation
1: Rotation autotuning
2: Static autotuning 1(autotune totally)
3: Static autotuning 2(autotune part parameters)
0: Invalid
1: Valid during the whole procedure
Function
restore
parameter
0: No operation
1: Restore the default value
2: Cancel the fault record
P01 Group Start-up and stop control
0: Start-up directly
1: Start-up after DC braking
2: Start-up after speed tracing
Starting
frequency
of direct
start