Goodrive350-19 series VFD Function parameter list
- 207 -
Function
parameter
restoration
0: No operation
1: Restore to default value
2: Clear fault history
3: Lock keypad parameters
Note: After the selected function operations are
done, this function code will be restored to 0
automatically. Restoration to default value will
clear the user password, this function should be
used with caution.
7.2.2 P01 Start/stop control
0: Direct start
1: Start after DC brake
2: Start after speed-tracking 1
3: Start after speed-tracking 2
Note: It can be modified only after P11.26 is 1
indicating special functions are enabled.
Starting frequency
of direct start
Starting frequency of direct startup is the initial
frequency when the VFD starts. See P01.02 (hold
time of starting frequency) for details.
Setting range: 0.00–50.00Hz
Hold time of
starting frequency
Output frequency
fmax
t1
T
F1 set by P01.01
f1
T1 set by P01.02
A proper starting frequency can increase the
torque during startup. Within the hold time of