Goodrive350-19 series VFD Function parameter list
- 224 -
Flux-weakening
coefficient of
constant-power
zone
Used when asynchronous motor is in
flux-weakening control.
T
f
0.1
Flux-weakening
coefficient of motor
1.0
2.0
Min. flux-weakening limit of motor
P03.22 and P03.23 are valid during constant
power. When motor speed is above rated speed,
motor enters flux-weakening running state. The
flux-weakening control coefficient can change the
flux-weakening curvature, the larger the
coefficient, the steeper the curve, the smaller the
coefficient, the smoother the curve.
Setting range of P03.22: 0.1–2.0
Setting range of P03.23: 10%–100%
Min.
flux-weakening
point of
constant-power
zone
P03.24 sets the maximum output voltage of the
VFD, which is the percentage of rated motor
voltage. This value should be set according to field
conditions.
Setting range:0.0–120.0%
Carry out motor pre-exciting during starting to build
a magnetic field inside the motor to improve the
torque characteristics of motor during starting.
Setting range: 0.000–10.000s
Flux-weakening
proportional gain
Vector control
speed display
0: Display as per actual value
1: Display as per the set value