Goodrive350-19 series VFD Function parameter list
- 226 -
1: Reserved
Range: 0x0000–0x1111
Speed loop
differential gain
High-frequency
current loop
proportional
coefficient
Under closed-loop vector control mode (P00.00=3)
and P03.39, the current loop PI parameters are
P03.09 and P03.10; above P03.39, the PI
parameters are P03.37 and P03.38.
Setting range of P03.37: 0–65535
Setting range of P03.38: 0–65535
Setting range of P03.39: 0.0–100.0% (relative to
max. frequency)
High-frequency
current loop
integral coefficient
Current loop
high-frequency
switch-over point
Inertia
compensation
enable
Upper limit of
inertia
compensation
torque
Limit the max. inertia compensation torque to
prevent inertia compensation torque from being
too large.
Setting range: 0.0–150.0% (rated motor torque)
Inertia
compensation
filter times
Filter times of inertia compensation torque, used to
smooth inertia compensation torque.
Setting range: 0–10
Inertia
identification
torque value
Due to friction force, it is required to set certain
identification torque for the inertia identification to
be performed properly.
0.0–100.0% (rated motor torque)
Enable inertia
identification
0: No operation
1: Enable