Goodrive350-19 series VFD Function parameter list
- 230 -
current oscillation during certain frequencies,
which may lead to unstable motor operation, or
even VFD overcurrent, you can adjust these two
parameters properly to eliminate such
phenomenon.
Setting range of P04.10: 0–100
Setting range of P04.11: 0–100
Setting range of P04.12: 0.00Hz–P00.03 (Max.
output frequency)
High-frequency
oscillation control
factor of motor 1
Oscillation control
threshold of motor
1
V/F curve setup of
motor 2
This parameter defines the V/F curve of motor 2 of
the Goodrive350-19 series to meet various load
characteristic requirements.
0: Straight V/F curve
1: Multi-point V/F curve
2: Torque-down V/F curve (1.3
th
order)
3: Torque-down V/F curve (1.7
th
order)
4: Torque-down V/F curve (2.0
nd
order)
5: Customize V/F (V/F separation)
Note: Refer to the parameter description of
P04.01 and P04.02.
Setting range of P04.14: 0.0%: (automatic)
0.1%–10.0%
Setting range of 0.0%–50.0% (relative to rated
frequency of motor 2)
Motor 2 torque
boost cut-off
V/F frequency
point 1 of motor 2
Note: Refer to the parameter description of
P04.03–P04.08
Setting range of P04.16: 0.00Hz–P04.18
Setting range of P04.17:0.0%–110.0% (rated
voltage of motor 2)
Setting range of P04.18: P04.16–P04.20
V/F voltage point
1 of motor 2
V/F frequency
point 2 of motor 2