Goodrive350-19 series VFD Function parameter list
- 236 -
1: Enable
Note: The I/F mode is not applicable to conical
motor applications.
Current setting in
I/F mode for
asynchronous
motor 2
When I/F control is adopted for asynchronous
motor 2, this parameter is used to set the output
current. The value is a percentage in relative to the
rated current of the motor.
Setting range: 0.0–200.0%
Proportional
coefficient in I/F
mode for
asynchronous
motor 2
When I/F control is adopted for asynchronous
motor 2, this parameter is used to set the
proportional coefficient of the output current
closed-loop control.
Setting range: 0–5000
Integral coefficient
in I/F mode for
asynchronous
motor 2
When I/F control is adopted for asynchronous
motor 2, this parameter is used to set the integral
coefficient of the output current closed-loop
control.
Setting range: 0–5000
Starting frequency
for switching off
I/F mode for
asynchronous
motor 2
When I/F control is adopted for asynchronous
motor 2, this parameter is used to set the starting
frequency for switching off the output current
closed-loop control. When the frequency is lower
than the value of this parameter, the current
closed-loop control in the I/F control mode is
enabled; and when the frequency is higher than
that, the current closed-loop control in the I/F
control mode is disabled.
Setting range: 0.00–20.00 Hz
End frequency for
switching off I/F
mode for
asynchronous