Goodrive350-19 series VFD Function parameter list
- 241 -
83: Downward DEC limit position
84: Light load speed boost signal
85: Brake detection
86: Valid signal of PTC overtemperature
(Supporting only the terminals S5 – S8 of
EC-IO502-00)
87: Position synchronization pulse counting reset
88: Switchover between motors 1 and 3
89: Anti-snag protection input
Polarity of input
terminal
This function code is used to set the polarity of
input terminals.
When the bit is set to 0, input terminal polarity is
positive;
When the bit is set to 1, input terminal polarity is
negative;
0x000–0x3F
Set S1–S4, filter time of HDI terminal sampling. In
cases where interference is strong, increase the
value of this parameter to avoid mal-operation.
0.000–1.000s
0x000–0x3F (0: disable, 1: enable)
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
BIT2: S3 virtual terminal
BIT3: S4 virtual terminal
BIT4: HDIA virtual terminal
BIT5: HDIB virtual terminal
Used to set the 2/3 Wire control mode.
0: 2-Wire control 1; integrate enabling function with
direction. This mode is the most popular dual-line
mode. Direction of motor rotation is determined by
the defined FWD/REV terminal command.