EasyManua.ls Logo

INVT Goodrive350-19 Series - Page 255

INVT Goodrive350-19 Series
540 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive350-19 series VFD Function parameter list
- 248 -
Function
code
Name
Description
Default
value
Modify
limit frequency of
HDIB
P05.47
Upper limit
frequency of HDIB
P05.45 50.000KHz
50.000
KHz
P05.48
Corresponding
setting of upper
limit frequency of
HDIB
-300.0%300.0%
100.0%
P05.49
HDIB frequency
input filter time
0.000s10.000s
0.030s
P05.50
AI1 input signal
type
0: Voltage type
1: Current type
Note: You can set the AI1 input signal type
through the corresponding function code.
0
7.2.7 P06 Output terminals
Function
code
Name
Description
Default
value
Modify
P06.00
HDO output type
0: Open collector high-speed pulse output: Max.
frequency of the pulse is 50.00kHz. For details
about the related functions, see P06.27P06.31.
1: Open collector output: For details about the
related functions, see P06.02.
0
P06.01
Y output selection
0: Invalid
1: In running
2: In forward running
3: In reverse running
4: In jogging
5: VFD fault
0
P06.02
HDO output
selection
0
P06.03
Relay RO1 output
selection
1
P06.04
Relay RO2 output
5

Table of Contents

Related product manuals