After loose rope protection is enabled, loose rope 
detection is performed during hoist startup: 
When the hoist runs upward and reaches P93.26, 
torque detection is performed after the delay 
P93.28. If the detected status is non loose rope 
(Torque value > Loose rope torque P93.24 or 
P93.25 for downward running), normal ACC/DEC 
is performed. 
If the detected status is loose rope (Torque value 
<=  Loose  rope  torque  P93.24),  the  output 
frequency is restricted to P93.26 within P93.27. 
If  load  holding,  (Torque  value)  >  (Loose  rope 
torque  P93.24+2%),  is  detected  within  P93.27, 
normal ACC/DEC is performed from this time. 
If the time exceeds P93.27, normal ACC/DEC is 
performed from this time. 
P93.24  can  be  set  with  the  reference  to  the 
autotuning result P93.33. Generally,  the  value  of