Goodrive350-19 series VFD Function parameter list
- 383 -
Function
code
Name
Description
Default
value
Modify
reference point, during downward limit,
P93.18=0.00m)
P93.19
Loose rope
autotuning
0: Invalid
1: Autotuning for upward
2: Autotuning for downward
0
P93.20
Enabling loose
rope protection
02
0: Disable
1: Enable
2: Enable stable lifting protection
0
P93.21
Loose rope
detection method
02
0: Set through torque
1: Set through torque autotuning
2: Set through external signal detection (AI1)
0
P93.22
Upward fixed
value of external
loose rope signal
0.010.0V
0.0V
P93.23
Downward fixed
value of external
loose rope signal
0.010.0V
0.0V
P93.24
Torque setting for
upward loose
rope protection
After loose rope protection is enabled, loose rope
detection is performed during hoist startup:
When the hoist runs upward and reaches P93.26,
torque detection is performed after the delay
P93.28. If the detected status is non loose rope
(Torque value > Loose rope torque P93.24 or
P93.25 for downward running), normal ACC/DEC
is performed.
If the detected status is loose rope (Torque value
<= Loose rope torque P93.24), the output
frequency is restricted to P93.26 within P93.27.
If load holding, (Torque value) > (Loose rope
torque P93.24+2%), is detected within P93.27,
normal ACC/DEC is performed from this time.
If the time exceeds P93.27, normal ACC/DEC is
performed from this time.
P93.24 can be set with the reference to the
autotuning result P93.33. Generally, the value of
5.0%
P93.25
Torque setting for
downward loose
rope protection
5.0%
P93.26
Loose rope
protection
maintenance
frequency
15.00Hz
P93.27
Loose rope
protection
maintenance time
2.0s
P93.28
Loose rope
detection delay
0.5s