Goodrive350-19 series VFD Troubleshooting
- 396 -
Fault
code
Fault type
Possible cause
Corrective measure
card slot 3
however, it cannot read the
card type
Stabilize the extension card
interfaces after power down,
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes, replace
the insertion port after power
down
C1-Er
Communication
timeout occurred to
the extension card in
card slot 1
There is no data
transmission in interfaces of
card slot 1
Confirm whether the extension
card inserted can be supported;
Stabilize the extension card
interfaces after power down,
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes, replace
the insertion port after power
down
C2-Er
Communication
timeout occurred to
the extension card in
card slot 2
There is no data
transmission in interfaces of
card slot 2
Confirm whether the extension
card inserted can be supported;
Stabilize the extension card
interfaces after power down,
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes, replace
the insertion port after power
down
C3-Er
Communication
timeout occurred to
the extension card in
card slot 3
There is no data
transmission in interfaces of
card slot 3
Confirm whether the extension
card inserted can be supported;
Stabilize the extension card
interfaces after power down,
and confirm whether fault still