Goodrive350-19 series VFD Commissioning
- 71 -
torque verification time P90.30 is reached, the torque verification fault tPF is reported.
Torque
verification time
P90.30
Torque verification
delay 60ms
Torque (%)
Frequency (Hz)
In closed-loop mode, if the brake slip fault delay P93.01 is greater than 0, the brake slip detection
function is enabled. During torque verification, if the motor (encoder) speed exceeds the set brake slip
speed threshold P93.00 and the situation duration exceeds P93.01, the brake failure fault bE is
reported.
The torque verification and brake slip flowchart is as follows: