Goodrive350-19 series VFD Commissioning
- 90 -
User-
defined
function
list
Related
function
code
Name
Description
Setting
range
Default
A80.07
P04.40
Enabling I/F mode
for asynchronous
motor 1
01
01
0
A80.08
P04.41
Forward current
setting in I/F mode
for asynchronous
motor 1
0.0200.0%
0.0200.0%
120.0%
A80.09
P04.52
Reverse current
setting in I/F mode
for asynchronous
motor 1
0.0200.0%
0.0200.0%
120.0%
A80.10
P05.00
HDI input type
0x000x11
Ones: HDIA input type
0: HDIA is high-speed pulse
input
1: HDIA is digital input
Tens: HDIB input type
0: HDIB is high-speed pulse
input
1: HDIB is digital input
0x000x11
0
A80.11
P05.03
Function of S3
terminal
0: No function
1: Forward running
2: Reverse running
389: See chapter 7.
089
0
A80.12
P05.04
Function of S4
terminal
089
0
A80.13
P05.05
Function of HDIA
terminal
089
0
A80.14
P06.01
Y output selection
0: Invalid
1: In running
2: In forward running
3: In reverse running
464: See chapter 7.
066
0
A80.15
P06.03
RO1 output
selection
066
0
A80.16
P06.04
RO2 output
selection
066
0
A80.17
P10.02
Multi-step speed 0
0.0100.0%
0.0100.0
0.0%
A80.18
P10.04
Multi-step speed 1
0.0100.0%
0.0100.0
0.0%