Goodrive350-19 series VFD Commissioning
- 89 -
5.11.5 User-defined macros
You can enter user-defined function macro settings through P90.02.
Function
code
Name
Description
Default
P90.02
User-defined function
macro setting
03
0: None
1: Enter the settings of user-defined function
macro 1
2: Enter the settings of user-defined function
macro 2
3: Enter the settings of user-defined function
macro 3
0
When P90.02=1, you will automatically enter A80.00A80.41 to set related function codes.
When P90.02=2, you will automatically enter A81.00A81.41 to set related function codes.
When P90.02=3, you will automatically enter A82.00A82.41 to set related function codes.
Currently, there are 42 common function codes available for you to define macros. The three
user-defined macro tables are the same. The following lists A80.00A80.41.
User-
defined
function
list
Related
function
code
Name
Description
Setting
range
Default
A80.00
P00.00
Speed control mode
0: SVC mode 0
1: SVC mode 1
2: V/F control mode
3: Closed-loop vector control
mode
03
2
A80.01
P00.01
Command running
channel
0: Keypad
1: Terminal
2: Communication
02
0
A80.02
P00.06
Setting channel of A
frequency command
0: Keypad
114: See chapter 7.
15: Graded multi-step speed
015
0
A80.03
P00.11
ACC time 1
0.03600.0s
0.03600.0
10.0s
A80.04
P00.12
DEC time 1
0.03600.0s
0.03600.0
10.0s
A80.05
P01.05
ACC/DEC mode
0: Straight line
1: S curve
01
0
A80.06
P01.08
Stop mode
0: Decelerate to stop
1: Coast to stop
01
0