EasyManua.ls Logo

INVT SPC7K5TR46-H

INVT SPC7K5TR46-H
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SPC Series Solar Pump Inverter Function parameter list
-34-
P08 group Enhanced functions
Function
code
Name
Description
Default
Modify
P08.28
Auto fault reset
count
Setting range: 010
The following faults can be automatically
reset:
OC1: Overcurrent during acceleration
OC2: Overcurrent during deceleration
OC3: Overcurrent during constant speed
running
OV1: Overvoltage during acceleration
OV2: Overvoltage during deceleration
OV3: Overvoltage during constant speed
running
UV: Bus undervoltage fault
OL1: Motor overload
OL2: Inverter overload
SPO: Phase loss on output side
EF: External fault
CE: RS485 communication fault
ItE: Current detection fault
tE: Motor autotuning fault
EEP: EEPROM operation error
END: Running time reached
OL3: Electronic overload
ETH1: To-ground short-circuit fault 1
ETH2: To-ground short-circuit fault 2
dEu: Speed deviation fault
STo: Mal-adjustment fault
LL: Underload fault
5
P08.29
Auto fault reset
interval
0.13600.0s
10.0s

Table of Contents

Related product manuals