Modbus
Address
Decimal
Address
Hex Register Name Access Default
Value
Value
Range
Description
30301 300 0x12
C
TEMPERATURE_SEN
SOR
Read-
only
Actual temperature
sensor value with offset
30302 301 0x12
D
HUMIDITY_SENSOR Read-
only
Actual humidity sensor
value with offset
30303 302 0x12
E
CO2_SENSOR Read-
only
Actual CO2 sensor value
with offset
40304 303 0x12
F
TEMPERATURE_SEN
SOR_OFFSET
Read/
write
0 Temperature sensor
offset
40305 304 0x13
0
HUMIDITY_SENSOR
_OFFSET
Read/
write
0 Humidity sensor offset
40306 305 0x13
1
CO2_SENSOR_OFFS
ET
Read/
write
0 CO2 sensor offset
40307 306 0x13
2
TEMPERATURE_FILT
ER
Read/
write
60 Filtering time for the
temperature sensor
(seconds)
40308 307 0x13
3
HUMIDITY_FILTER Read/
write
60 Filtering time for the
humidity sensor
(seconds)
40309 308 0x13
4
CO2_FILTER Read/
write
60 Filtering time for the
CO2 sensor (seconds)
40316 315 0x13
B
TEMPERATURE_CO
NFIGURATION
Read/
write
17
Bit Name 0 1
0 ACTIVE Not active Active
(def)
Activates/deactivates the
sensor
4 THIRD_POINT-
ACTIVE
No decimal Decimal
(def)
Sets decimal places
40317 316 0x13
C
HUMIDITY_CONFIG
URATION
Read/
write
17
Bit Name 0 1
0 ACTIVE Not active Active
(def)
Activates/deactivates the
sensor
4 THIRD_POINT-
ACTIVE
No decimal Decimal
(def)
Sets decimal places
40318 317 0x13
D
CO2_CONFIGURATI
ON
Read/
write
1