Modbus
Address
Decimal
Address
Hex Register Name Access Default
Value
Value
Range
Description
40217 216 0xD8 REFRESH_TIME 5 1-60 Sets the duration of the
display time of particular
parameters
40219 218 0xDA ICON_DISPLAY Read/
write
Bit Name 0 1
8 ECO Not active Active Switches on/off an ECO
LED
40226 225 0xE1 CO2_SETPOINT_FO
R_ALARM
Read/
write
1500 CO2 alarm setpoint
40227 226 0xE2 CO2_HYSTERESIS_F
OR_ALARM
Read/
write
100 CO2 alarm hysteresis
30230 229 0xE5 ALARM_STATUS Read-
only
CO2 current alarm
status
30231 230 0xE6 NAVIGATIONAL_LE
D_MODE
Read/
write
1 0-4 Sets a mode of the
navigational LED
Bit Name 0 1
0 OFF Not active Active
1 ON (default) Not active Active
2 Active on IDLE and
STANDBY
Not active Active
3 Active on IDLE only Not active Active
4 Active on STANDBY
only
Not active Active
30232 231 0xE7 NAVIGATIONAL_LE
D_BRIGHTNESS
Read/
write
100 0-100 Navigational LED
brightness
30233 232 0xE8 NAVIGATIONAL_LE
D_RED
Read/
write
100 0-100 Navigational LED color -
red component intensity
30234 233 0xE9 NAVIGATIONAL_LE
D_GREEN
Read/
write
100 0-100 Navigational LED color -
green component
intensity
30235 234 0xE1
0
NAVIGATIONAL_LE
D_BLUE
Read/
write
100 0-100 Navigational LED color -
blue component
intensity