EasyManua.ls Logo

iSMA CONTROLLI TP - Page 45

iSMA CONTROLLI TP
49 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TP Software User Manual
www.ismacontrolli.com
DMP253en | 1st Issue rev. 0 | 04/2022
BACnet
Type & ID
BACnet
Property
Decimal
Address
Hex Object
Name
Access Default
Value
Value
Range
Description
BO22 Present
Value
ECO Switches on
an ECO LED
AO17 Present
Value
223 0xDF EXIT_EDIT_TIM
E
Read/
write
Sets the time
after which
edition of any
editable
parameter is
finished
AO19 Present
Value
225 0xE1 CO2_SETPOIN
T_FOR_ALARM
Read/
write
1500 CO2 alarm
setpoint
AO20 Present
Value
226 0xE2 CO2_HYSTERE
SIS_FOR_ALAR
M
Read/
write
100 CO2 alarm
hysteresis
BI0 Present
Value
229 0xE5 ALARM_STATU
S
Read-
only
CO2 current
alarm status
MSV5 Present
Value
230 0xE6 NAVIGATIONA
L_LED_MODE
Read/
write
1 0-4 Sets a mode
of the
navigational
LED
AO22 Present
Value
231 0xE7 NAVIGATIONA
L_LED_BRIGHT
NESS
Read/
write
100 0-100 Navigational
LED
brightness
AO23 Present
Value
232 0xE8 NAVIGATIONA
L_LED_RED
Read/
write
100 0-100 Navigational
LED color -
red
component
intensity
AO24 Present
Value
233 0xE9 NAVIGATIONA
L_LED_GREEN
Read/
write
100 0-100 Navigational
LED color -
green
component
intensity
AO25 Present
Value
234 0xE1
0
NAVIGATIONA
L_LED_BLUE
Read/
write
100 0-100 Navigational
LED color -
blue
component
intensity
AI4 Present
Value
300 0x12
C
TEMPERATURE
_SENSOR
Read-
only
Actual
temperature
sensor value
with offset
AI5 Present
Value
301 0x12
D
HUMIDITY_SEN
SOR
Read-
only
Actual
humidity