TP Software User Manual
www.ismacontrolli.com
DMP253en | 1st Issue rev. 0 | 04/2022
BACnet
Type & ID
BACnet
Property
Decimal
Address
Hex Object
Name
Access Default
Value
Value
Range
Description
sensor value
with offset
AI6 Present
Value
302 0x12
E
CO2_SENSOR Read-
only
Actual CO2
sensor value
with offset
AI4 4205 303 0x12
F
TEMPERATURE
_SENSOR_OFF
SET
Read/
write
0 Temperature
sensor offset
AI5 4205 304 0x13
0
HUMIDITY_SEN
SOR_OFFSET
Read/
write
0 Humidity
sensor offset
AI6 4205 305 0x13
1
CO2_SENSOR_
OFFSET
Read/
write
0 CO2 sensor
offset
AI4 4003 306 0x13
2
TEMPERATURE
_FILTER
Read/
write
60 Filtering time
for the
temperature
sensor
(seconds)
AI5 4003 307 0x13
3
HUMIDITY_FILT
ER
Read/
write
60 Filtering time
for the
humidity
sensor
(seconds)
AI6 4003 308 0x13
4
CO2_FILTER Read/
write
60 Filtering time
for the CO2
sensor
(seconds)
315 0x13
B
TEMPERATURE
_CONFIGURATI
ON
Read/
write
AI4 Out Of
Service
ACTIVE 1 Activates/
deactivates
the sensor
AI4 4202 THIRD_POINT_
ACTIVE
Sets decimal
places
316 0x13
C
HUMIDITY_CO
NFIGURATION
Read/
write
AI5 Out Of
Service
ACTIVE 1 Activates/
deactivates
the sensor
AI5 4202 THIRD_POINT_
ACTIVE
Sets decimal
places