TP Software User Manual
www.ismacontrolli.com
DMP253en | 1st Issue rev. 0 | 04/2022
BACnet
Type & ID
BACnet
Property
Decimal
Address
Hex Object
Name
Access Default
Value
Value
Range
Description
317 0x13
D
CO2_CONFIGU
RATION
Read/
write
AI6 Out Of
Service
ACTIVE 1 Activates/
deactivates
the sensor
AO27 Present
Value
322 0x14
2
BUZZER_VOLU
ME
Read/
write
50 0-100 Buzzer
volume (%)
AO28 Present
Value
323 0x14
3
BUZZER_FREQ
UENCY
Read/
write
400 20-200
00
Buzzer
frequency
(Hz)
Device 3020 1301 0x51
5
FLASH_HW_VE
RSION
Read-
only
HW version
AV56 Present
Value
1500 0x5D
C
SETPOINT_VAL
UE
Read/
write
0-500 Temperature
setpoint
value
AI 3 Present
Value
1501 0x5D
D
EFFECTIVE_SET
POINT
Read-
only
Sum of
setpoint and
offset values
AV 57 Present
Value
1502 0x5D
E
DEFAULT_SETP
OINT
Read/
write
210 0-500 Default
temperature
setpoint
AV 58 Present
Value
1503 0x5D
F
OFFSET_SETPO
INT
Read/
write
0 0-500 Temperature
offset for
setpoint
AV 56 Low Limit 1504 0x5E
0
SETPOINT_LO
W_LIMIT
Read/
write
180 Min. available
setpoint
value
AV 56 High Limit 1505 0x5E
1
SETPOINT_HIG
H_LIMIT
Read/
write
240 Max. available
setpoint
value
AV 59 Present
Value
1506 0x5E
2
OFFSET_RANG
E
Read/
write
30 0-500 Limits offset
value
AV 56 4206 1507 0x5E
3
SETPOINT_STE
P
Read/
write
10 Setpoint step
value
1512 0x5E
8
SETPOINT_CO
NFIGURATION
Read/
write
Setpoint
configuration
of
parameters:
Visible,
Editable,
Operating