TrimmingtheUpperandLowerBafes
Toimproveuedrawandsmokedischargethelowerandupperbafesmaybetrimmedbackeachend.Allow
theappliancetocool.Removethelowerandupperbafesasdescribedintheappliancepreparationsection.
Theupperbafemaybetrimmedbackby15mmto25mmeachendandeachlowerboardbafetrimmedback
10mmto15mmfromtheirouteredges.Trimmingcanbecarriedoutusingnormalwoodcuttinghandtools.Ret
thebafesandretest.Thisisnotasolutiontoovercomepoorchimneydesign.Ifafterfurtherretestingthis
cannot be resolved then further investigation will be required or seek expert advice. Advise the customer not to
usethereuntilexpertadvicehasbeensought.
Trimmingthelowerbafessidesandfrontedges
Upperbafeboard Trimmingtheupperbafe
Notice Plate
Ensure that any notice plate is provided in line with the building regulations J4. The notice should contain
informationontheperformancecharacteristicsofthehearth,replace,ueorchimneyandistobexedinan
appropriate place.
Carbon Monoxide (CO) Alarm
Fit a carbon monoxide (CO) alarm in the room where the appliance is located. Adhere to local regulations and
the manufacturers instructions when siting the detector position.
Cleaning Up
Immediatelyafterinstallation,thevisiblepartsofthereshouldbecleanedup.Thereafter,thesurfacesmaybe
kept clean by using a light brush to remove dust and by occasional wiping with a lint-free cloth.
Lighting after installation
The Jetmaster should not be run hard until any surrounding cement and plasterwork is completely dry and
cured.
A. 7 days drying time if the house has other forms of heating.
B. Atleast14daysiftheinstallationisinaneworunoccupiedproperty,oristtedintoacompletelynew
chimney breast.
21