EasyManua.ls Logo

Jntech JNP22KH-V5 - Page 71

Jntech JNP22KH-V5
98 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
71
WC-Set
WC-Set
RunMode
=CVT
=MPPT
UINST
The instruction voltage of the array, used for
the operating voltage point of the instruction
array.
CVT mode
works
F-limit
Frequency limit, the maximum frequency that
the inverter can output. the default value is
"50Hz"or"60Hz"
D-mode
When the user's PHOTOVOLTAIC water pump
system adopts external water level sensor to
realize the dry protection of the water pump,
the dry protection mode shall be set to "test".
D-power
When the user's photovoltaic pump inverter
matches the pump with lower power, this
parameter needs to be reset. The
recommended setting is 40% of the rated power
of the pump. For example, the drying power of
7.5KW water pump can be set to 3000.
D-time
Beat dry recovery time.
Under automatic beating mode: the interval
time of starting and running of the inverter
again after the inverter is stopped by beating
alarm, the unit is minutes. The factory default is
30 minutes.
Detection in the beating mode: the interval time
(in minutes) between the inverter receiving the

Table of Contents

Related product manuals