EasyManua.ls Logo

Johnson Controls 100 Series - Page 52

Johnson Controls 100 Series
102 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
52
FORM100.50-EG12 (918)
TABLE 16 - YPAL070–105: DDP402-9-100 DIRECT DRIVE PLENUM (DDP) SUPPLY FAN
TOTAL STATIC PRESSURE (IWG)
CFM
STD. AIR
1.0 2.0 3.0 4.0 5.0 6.0
BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM
14,000 557 3.5 672 6.5 790 10.1 906 14.1 1,013 18.3 1,109 22.8
16,000 604 4.3 706 7.6 807 11.2 911 15.4 1,013 20.0 1,110 24.8
18,000 652 5.2 748 8.8 836 12.6 927 16.9 1,019 21.6 1,111 26.7
20,000 701 6.2 792 10.1 873 14.2 953 18.7 1,035 23.5 1,118 28.8
22,000 751 7.3 839 11.6 915 16.0 987 20.7 1,060 25.7 1,134 31.0
24,000 801 8.5 887 13.3 959 18.0 1,026 23.0 1,093 28.1 1,159 33.6
26,000 852 9.9 936 15.1 1,005 20.2 1,069 25.5 1,131 30.9 1,192 36.5
28,000 905 11.5 985 17.1 1,053 22.6 1,114 28.2 1,172 33.9 1,229 39.8
30,000 958 13.3 1,034 19.3 1,101 25.2 1,160 31.1 1,216 37.1 1,270 43.3
32,000 1,012 15.4 1,084 21.6 1,150 28.0 1,208 34.3 1,261 40.6 1,313 47.1
NOTE: For performance at operating points not included in these tables, consult your local Johnson Controls representative.
TABLE 17 - YPAL070–105: DDP402-9-120 DIRECT DRIVE PLENUM (DDP) SUPPLY FAN
TOTAL STATIC PRESSURE (IWG)
CFM
STD. AIR
1.0 2.0 3.0 4.0 5.0 6.0
BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM
18,000 596 4.8 699 8.5 803 12.8 909 17.6 1,013 22.9
20,000 637 5.7 734 9.7 826 14.1 920 19.1 1,016 24.5 1,110 30.3
22,000 680 6.6 772 11.0 856 15.7 940 20.7 1,026 26.3 1,113 32.3
24,000 723 7.7 813 12.5 890 17.4 966 22.6 1,044 28.3 1,123 34.4
26,000 766 8.9 854 14.1 927 19.3 998 24.8 1,069 30.6 1,141 36.9
28,000 810 10.2 895 15.8 967 21.4 1,033 27.1 1,098 33.2 1,164 39.6
30,000 854 11.6 937 17.6 1,009 23.6 1,070 29.7 1,132 36.0 1,193 42.5
32,000 899 13.2 981 19.7 1,049 26.0 1,109 32.4 1,168 39.0 1,225 45.8
34,000 945 15.0 1,024 21.8 1,090 28.6 1,151 35.4 1,205 42.2 1,260 49.3
36,000 991 16.9 1,132 31.3 1,132 31.3 1,192 38.5 1,245 45.7 1,296 53.0