Hot Water Heat – For applications where hot water is available for heating, a hot water
heating coil is available. A range of coil fin count selections are available to properly size the
heating for the application. Units with hot water heat are ETL listed.
Steam Heat – For applications where steam is available for heating, a steam heating coil
is available. A range of coil fin count selections are available to properly size the heating
for the application. Units with steam heat are ETL listed.
POWER OPTIONS
Single-Point Supply with Terminal Block This configuration is standard, and includes
three terminals for the incoming 3-phase power and is the standard configuration for the
Series 100 product. It includes the enclosure, terminal-block, and interconnecting wiring
to the compressors, heater and furnace controls, all fans, etc. In this configuration, code
requires that a means of disconnect (not provided) must be installed at the site within line-
of-sight of the equipment.
Single-Point Supply with Non-Fused Disconnect Switch This option is the same as
the single-point with terminal block option except it includes a unit-mounted through-the-
door manual non-fused disconnect switch with an external, lockable handle (in compli-
ance with Article 440-14 of N.E.C.). This option provides a means to isolate the unit power
voltage for servicing. Others must supply separate external fusing which must comply with
the National Electric Code and/or local codes.
Dual-Point Supply with Terminal Block – This option includes enclosure, terminal blocks
circuited to the supply and exhaust fans and control transformer and a second set of
terminal blocks with interconnecting wiring to the compressors, heat (if applicable) and
condenser.
Convenience Outlet – This options includes a powered 115V GFCI convenience outlet
that can be used for powering tools or lights for servicing. A protective cover plate is in-
cluded while not in use. The outlet is located on the bottom left hand corner of the power
panel.
CONTROL FEATURES AND OPTIONS
Microprocessor-Based Single Package Unit Controller All Series 100 units are
equipped with a factory-installed, programmed and commissioned unit controller with all I/O
capabilities and control sequences. The controls include all on-board diagnostic, safety and
control features to operate the single package unit. A multimedia card interface is included
for software upgrades and can be used for data logging to simplify equipment troubleshoot-
ing. Communication ports are included as standard with three alarm outputs, a shutdown
contact, remote start/stop input, smoke ventilation controls, analog inputs for supply air
temperature and duct static pressure rest, along with a variety of other capabilities.
Standard Ambient YPAL070–105 models operate down to 45.0°F as standard.
Low Ambient on Circuits One, [One and Two], or [One, Two, and Three] – This op-
tion includes low ambient control of the first [first and second] [first, second, and third]
circuit(s) down to 0.0°F through the use of suction and discharge pressure transducers
on the circuit(s).
Pressure Transducers with Readout Capability This option includes suction and dis-
charge pressure transducers on each circuit and provides pressure readout of all circuits
at the unit control panel.

Other manuals for Johnson Controls 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls 100 Series and is the answer not in the manual?

Johnson Controls 100 Series Specifications

General IconGeneral
BrandJohnson Controls
Model100 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals