For Powered Exhaust or Return Fan Options Above, Use The Following
1. Fan Motor: Fan motors shall be NEMA design ball-bearing types with electrical
characteristics and horsepower as specied. Motors shall be 1750 RPM, open drip-
proof type [TEFC]. [Optional shaft grounding rings on motors increase motor lon-
gevity when applied with a VFD.] The motor shall be located within the unit on an
adjustable base.
Mountings: Fan and fan motor shall be internally mounted and isolated on a full
width isolator support channel using 1-inch springs [2-inch springs and seismic
restraints]. The fan discharge shall be connected to the fan cabinet using a flexible
connection to insure vibration-free operation.
Bearings and Drives: Fan bearings shall be self-aligning, pillow block or flanged
type regreaseable ball bearings and shall be designed for an average life (L50) of
at least 200,000 hours. All bearings shall be factory lubricated and equipped with
standard hydraulic grease fittings and lube lines extended to the motor side of the
fan. Fan drives shall be selected for a 1.5 service factor and anti-static belts shall be
furnished. All drives shall be fixed pitch. Fan shafts shall be selected to operate well
below the first critical speed and each shaft shall be factory coated after assembly
with an anti-corrosion coating.
Filter Section
Select a Filter Rack, Filter Media, and Switch if Desired
1. Angled Filter Rack: Two-inch throwaway lters shall be provided in an angled lter
rack.
2. Angled Filter Rack: Two-inch cleanable lters shall be provided in an angled lter
rack.
3. Angled Filter Rack: Two-inch MERV 8 carbon media lters shall be provided in an
angled lter rack.
4. Angled Filter Rack: Two-inch high efciency (30%) MERV 8 pleated lters shall be
provided in an angled lter rack.
5. Flat Filter Rack: 60–65% Efcient MERV 11 Rigid Filters with a two-inch high ef-
ciency MERV 8 pleated pre-lters shall be provided in a at lter rack.
6. Flat Filter Rack: 90–95% Efcient MERV 14 Rigid Filters with a two-inch high ef-
ciency MERV 8 pleated pre-lters shall be provided in a at lter rack.
7. Dirty Filter Alarm: A dirty lter switch shall be provided and wired to the single
package unit control panel. Upon closure of the switch, the controller shall display
a dirty lter fault. The setting of the switch can be changed manually to close at a
specied pressure drop across the lters.
Evaporator Section
1. Cooling Coil: Evaporator coils shall be direct expansion type with intertwined circu-
iting to assure complete coil face activity during part load operation. Coil tubes shall
be 3/8-inch OD copper, with internally enhanced tubes. Fins shall be enhanced me-
chanically expanded to bond with the copper tubes. Coil casing shall be fabricated
from heavy gauge galvanized steel. All coils shall be pressure tested at a minimum
of 450 psig.