Hardware Installation—Installing the IFC-1010/2020
87
Figure 61 illustrates an M500MJ monitoring normally open contact fire
alarm initiating devices that do not require power and an M502MJ
monitoring powered two wire smoke detectors. Refer to Figure 63 for
circuits using four wire detectors.
Notes: For additional ratings, refer to Circuit/Device Ratings and
Connections Technical Bulletin (LIT-448160).
For connection of the initiating devices, refer to the manufacturer’s
installation instructions packaged with each device.
For M502MJ, mount the appropriate EOLR across Terminals 8 and 9.
For more information, refer to 500 Series Intelligent Modules
Technical Bulletin (LIT-408100).
M502MJ
1
5
2
6
3
7
4
8
9
SLC Loop Channel A
Supervised and Power-limited
M500MJ
1
5
2
6
3
7
4
8
9
LB P2-3 (-)
LB P2-1 (+)
Heat Detector Pull Station
SLC
24 VDC Two Wire Smoke Detectors
idcd
47K ohm
EOLR
3.9K ohm
0.5 watt
UL Listed 24 VDC Regulated Power
Limited Power Supply for
Fire Protective Signaling
or
MPS-24A/E, TB3 Terminal 1 (+) and 2 (-)
APS-6R, TB2 Terminal 1 (+) and 2 (-)
Terminal 3 (+) and 4 (-)
Power-limited
Resettable Power
Figure 61: NFPA Style D Initiating Device Circuit
Note: A SLC control point (M510CJ or XPR-8) with a Type ID or
PWRC is necessary to control power to the detectors to execute a
system reset when using the APS-6R. (see Figure 62).

Table of Contents

Other manuals for Johnson Controls IFC-2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls IFC-2020 and is the answer not in the manual?

Johnson Controls IFC-2020 Specifications

General IconGeneral
BrandJohnson Controls
ModelIFC-2020
CategoryControl Panel
LanguageEnglish

Related product manuals